石高扬, 谢强. 特高压GIS套管内绝缘失效地震易损性分析[J]. . DOI: 10.6052/j.issn.1000-4750.2023.07.0532
引用本文: 石高扬, 谢强. 特高压GIS套管内绝缘失效地震易损性分析[J]. . DOI: 10.6052/j.issn.1000-4750.2023.07.0532
SHI Gao-yang, XIE Qiang. SEISMIC VULNERABILITY ANALYSIS OF INTERNAL INSULATION FAILURE OF ULTRA-HIGH VOLTAGE GIS BUSHING[J]. Engineering Mechanics. DOI: 10.6052/j.issn.1000-4750.2023.07.0532
Citation: SHI Gao-yang, XIE Qiang. SEISMIC VULNERABILITY ANALYSIS OF INTERNAL INSULATION FAILURE OF ULTRA-HIGH VOLTAGE GIS BUSHING[J]. Engineering Mechanics. DOI: 10.6052/j.issn.1000-4750.2023.07.0532

特高压GIS套管内绝缘失效地震易损性分析

SEISMIC VULNERABILITY ANALYSIS OF INTERNAL INSULATION FAILURE OF ULTRA-HIGH VOLTAGE GIS BUSHING

  • 摘要: 特高压套管外套筒-导电杆体系在地震作用下存在电气功能失效的风险。为了研究导电杆位移引起的套管内绝缘失效,建立外套筒-导电杆耦联体系理论模型,利用±1100 kV复合材料GIS套管振动台试验和有限元分析进行模型验证,研究外套筒-导电杆相互作用机理及地震易损性,结果表明:地震作用下套管内绝缘失效模式主要来源于:外套筒顶部位移引起的导电杆变形、导电杆自身受到的地震激励,其中外套筒顶部位移是引起内绝缘失效的主要原因;外套筒与导电杆的相对位移沿着高度呈现出近似抛物线分布规律,最大值点位于套管重心下部;相同地震强度作用下,特高压套管内绝缘失效概率介于套管根部断裂和顶部牵拉失效概率之间。外套筒-导电杆体系相对位移的地震响应可以通过建立耦联体系理论模型求得,应该同时关注内绝缘失效和套管根部断裂失效对电气功能的影响。

     

    Abstract: The outer sleeve-conductor system of ultra-high voltage (UHV) bushing has the risk of electrical function failure under seismic action. In order to study the internal insulation failure mode of UHV bushing caused by the excessive displacement, a simplified theoretical model of an outer sleeve-conductor coupled system is established, and its analysis results are verified by a ±1100 kV UHV gas-insulated switchgear (GIS) composite bushing shaking table test and by the finite element method. The interaction mechanism and seismic vulnerability of the outer sleeve-conductor system are studied. The study results show that the main failure modes of internal insulation under seismic action are caused by two aspects: a) the deformation of the conductor caused by displacement at top of the outer sleeve; b) the seismic excitation of the conductor itself. And the former is the main cause of internal insulation failure. The relative displacement of the outer sleeve and the conductor shows an approximate parabolic distribution along the height, and the maximum point is located at the lower part of the bushing gravity center. Under the actions of the same PGA, the failure probability of internal insulation is between the failure probability of fracture at the bottom and the traction at the top of the bushing. The seismic response of relative displacement between the outer sleeve and conductor can be obtained by the simplified theoretical model, and attention should be paid to both internal insulation and fracture failure modes.

     

/

返回文章
返回
Baidu
map